DESCRIPTION | UNIT | VALUE | VALUE | VALUE | VALUE | VALUE | |
1 | GENERAL |
| 3×35 + 1×16 + NA25 mm2 | 3×50 + 1×16 + NA35mm2 | 3×70 + 1×16 + NA50 mm2 | 3×25 + 1×16 + NA25 mm2 | 3X120 + 1X16 + NA70 mm2 |
| Manufacturing standard |
| NTP 370.254 | NTP 370.254 | NTP 370.254 | NTP 370.254 | NTP 370.254 |
2 | DESIGNATION | CAAI | CAAI | CAAI | CAAI | CAAI | |
| Rated Voltage Uo / U | kV | 0.6 / 1 | 0.6 / 1 | 0.6 / 1 | 0.6 / 1 | 0.6 / 1 |
3 | TERMS OF USE | ||||||
| Maximum temperature in permanent regime. | ° C | 90 | 90 | 90 | 90 | 90 |
| Maximum temperature in overload regime. | ° C | 130 | 130 | 130 | 130 | 130 |
| Maximum temperature in short-circuit mode (5 s) | ° C | 250 | 250 | 250 | 250 | 250 |
4 | CABLES GATHERING: | ||||||
| Maximum wireways, depending on the diameter of thePhase wire | Times | 60 | 60 | 60 | 60 | 60 |
5 | PHASE CABLE: | ||||||
| Standard | NTP IEC 60228 | NTP IEC 60228 | NTP IEC 60228 | NTP IEC 60228 | NTP IEC 60228 | |
| Material | Pure uncoated aluminum | Pure uncoated aluminum | Pure uncoated aluminum | Pure uncoated aluminum | Pure uncoated Aluminum | |
| Nominal section | mm2 | 35 | 50 | 70 | 25 | 120 |
| Class | 2 | 2 | 2 | 2 | 2 | |
| Minimum number of wires | No. | 7 | 6 | 12 | 6 | 15 |
| Maximum electrical resistance in DC at 20 ° C | Ohm / km | 0.868 | 0.641 | 0.443 | 1.20 | 0.253 |
| Insulation | ||||||
| Material | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | ||
| XLPE requirement | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | ||
| Minimum content of carbon black in XLPE | % | 2 | 2 | 2 | 2 | 2 | |
| Minimum average thickness | mm | 1.14 | 1.52 | 1.52 | 1.14 | 2.03 | |
| Minimum thickness at one point | mm | 1.03 | 1.37 | 1.37 | 1.03 | 1.83 | |
6 | STREET LIGHT CABLE | ||||||
| Standard | NTP IEC 60228 | NTP IEC 60228 | NTP IEC 60228 | NTP IEC 60228 | NTP 370.250 | |
| Material | Pure Aluminum without Coating | Pure uncoated aluminum | Pure uncoated aluminum | Pure uncoated aluminum | Pure uncoated aluminum | |
| Nominal section | mm2 | 16 | 16 | 16 | 16 | 16 |
| Class | 2 | 2 | 2 | 2 | 2 | |
| Minimum number of wires | No. | 7 | 6 | 6 | 6 | 6 |
| Maximum electrical resistance in DC at 20 ° C | Ohm / km | 1.91 | 1.91 | 1.91 | 1.91 | 1.91 |
| Insulation | ||||||
| Material | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | |
| XLPE requirement | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | |
| Minimum content of carbon black in XLPE | % | 2 | 2 | 2 | 2 | 2 |
| Minimum average thickness | mm | 1.14 | 1.14 | 1.14 | 1.14 | 1.14 |
| Minimum thickness at one point | mm | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 |
7 | NEUTRAL CABLE SUPPORT | ||||||
| Standards | NTP 370.258 | NTP 370.258 | NTP 370.258 | NTP 370.258 | NTP 370.258 | ||
| Cable Material | Aluminium alloy | Aluminium alloy | Aluminium alloy | Aluminium alloy | Aluminium alloy | ||
| Conductivity | % IACS | 52.5 | 52.5 | 52.5 | 52.5 | 52.5 | |
| Nominal section | mm2 | 25 | 35 | 50 | 25 | 70 | |
| Number of wires | 7 | 7 | 7 | 7 | 7 | ||
| Wire diameter | mm | 2.13 | 2.52 | 3,023 | 2.13 | 3.57 | |
| Minimum tensile strength | kN | 7.72 | 10.81 | 15.44 | 7.72 | 20.95 |
| Nominal Mass | kg / km | 68.4 | 95.7 | 136.8 | 68.4 | 191.5 |
| Density at 20 ° C | kg / m3 | 2703 | 2703 | 2703 | 2703 | 2703 |
| Electrical resistivity at 20 ° C | Ωmm2 / m | 0.032840 | 0.032840 | 0.032840 | 0.032840 | 0.032840 |
| Maximum electrical resistance in DC at 20 ° C | Ω / km | 1.3511 | 0.9651 | 0.6755 | 1.3511 | 0.4825 |
| Insulation | ||||||
| Material | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | Cross-linked polyethylene XLPE | ||
| XLPE requirement | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | According to table 2 of NTP 370.254 | ||
| Minimum content of carbon black in XLPE | % | 2 | 2 | 2 | 2 | 2 | |
| Minimum average thickness | mm | 1.14 | 1.14 | 1.52 | 1.14 | 1.52 | |
| Minimum thickness at one point | mm | 1.03 | 1.03 | 1.37 | 1.03 | 1.37 |
Product detail pictures:

Related Product Guide:
Fast and fantastic quotations, informed advisers to help you choose the correct products that suits all your needs, a short manufacturing time, responsible good quality control and distinct companies for paying and shipping affairs forOEM Famous G3 Module Quotes –Self-Supporting Aluminum Cable– Holley, The product will supply to all over the world, such as: Kuwait, Sacramento, Victoria, Insisting on the high quality generation line management and customers expert assistance, we now have designed our resolution to supply our buyers using the to start with amount getting and just after services practical experience. Maintaining the prevailing friendly relations with our buyers, we however innovate our solution lists all of the time to satisfy the brand new demands and adhere to the most up-to-date development of the market in Malta. We have been ready to face the worries and make the improve to understand all the possibilities in international trade.